YJV Power Cable
YJV power cable
1.Type:YJV
2.Standards implemented:
GB/T12706-2008
1.Application:
The products are used for rated voltages up to and including 1 KV as power lines to carry electric power. The flame retardant power cables are especially suitable for use in hotels,railway station,chemical plants,oil refinery petrochemical plants,mines,power stations,sub-ways and high-rises where flame retardant cables are required.
Installed in indoor/outdoor tunnel,cable trench or buried in loose soil.Single core cable is not allowed to be installed in magnetic conduit.
2.Service characteristics
The long-term permissible operating temperature of the conductor shall be 90℃.
The conductor temperature in short circuit:<=250℃,last time:<=5s;
Min.allowable bending radius;
20 times cable overall diameter,for single core cables
15 times cable overall diameter,for multi core cables
The ambient temperature for cable installation shall be not less than 0℃
The cable may be installed irrespective the drop in elevation