6*2*1.5mm2
Implementation standard: Q/321084KKA01-1996 standard is equivalent to the British BS5308-86 and Japanese electrical industry standard JCS258B
Product Usage: Multi-pair shielded cables suitable for signal transmission and detection instruments and instrument lights in industrial and mining enterprises such as power generation, metallurgy, and petrochemical enterprises for distribution DCS systems, electronic computer systems, and automation systems
Usage characteristics: rated voltage U. /U:450/750V
Maximum working temperature: general type does not exceed 70℃, cross-linked polyethylene does not exceed 90℃, heat-resistant 105℃ maximum does not exceed 105℃
Minimum ambient temperature: fixed installation -40℃, non-fixed installation -15℃
Minimum bending radius: The unarmored cable should be no less than 6 times the outer diameter of the cable, and the armored cable should be no less than 12 times the outer diameter of the cable